Backup capacity with average power consumption of 10 mA (basic set
of 5 sensors, 10 min measuring interval) is 130 hours. The battery can
be charged with the logger.
Additional Internal Battery
The additional internal battery QMB102 is easily installed to the
existing DIN-rail inside the tubular enclosure. The in-built battery
charger on the MAWS logger will charge the additional battery as well.
0402-023
Figure 6 Additional Internal Battery QMB102
Wall Adapter
A usual wall adapter (110/230 VAC, output min. 12 V/500 mA) can be
used when the distance to the MAWS system is less than 100 m
(328 ft.), provided that the wall adapter can be installed indoors.
NOTE
When a 12 V backup battery is used, it is recommended that QMB101
is disconnected by removing the red battery connector from the CPU.
This way the current consumption will be reduced when the charging
circuits of QMB101 are not in use.
NOTE
When the power cable resistance exceeds 10 Ω, a capacitor (from 100
to 200 µF, 40 V) should be added between GND and +ExtDC pins.
Make sure that the polarity is correct.