Chapter 7 ___________________________________________________________ Troubleshooting
VAISALA______________________________________________________________________ 183
- Open the logger cover and press the reset button. Refer to
section Resetting MAWS on page 192. After a few
seconds, the terminal should start to display logger
startup messages.
c. MAWS is not sending anything (nothing is seen on the
screen).
- After MAWS has been without power, for example when
you start it for the first time, check the time and date.
Timed operations will not work if the correct time is not
set.
- The setup is faulty. Press and keep down the reset button
for a few seconds. MAWS will restart and display the text
Using blank configuration.
d. The logger starts up normally, but sends error messages
during startup, for example, !Erroneous setup file.
- Reload the setup.
- Set the station parameters.
- Restart the system.
e. After uploading a new setup file, MAWS Terminal displays
Unhandled exception number: 39.
- The setup might include too many calculations; consider
removing some calculations.
- The interval between the statistical calculations is too
short, consider executing the calculations less frequently.
You might, for example, avoid calculations which are
executed more frequently than the results are reported or
logged.
f. If there are communication modules present, disconnect the
power and replace the modules.
- Replace one module at a time and try to restart the system
to find out the damaged one.
- Restart the system.