Seitenansicht 33
HUMIDITY
528
HUMIDITY
9
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
March 2014
J1
12-28
VDC
4-20 mA
RH signal
Optional
temperature
sensor to
controller
V+
TTRH
THRM THRM
24 VDC
Power
supply
ROOM, DUCT, AND OSA 3% HUMIDITY TRANSMITTERS
KH3 SERIES
Accuracy 3% RH @ 73°F from 5% to 90% RH;
(0%-5% & 90%-100%) add 4%
Drift <±0.5% per year
Thermal Effect 0.05% per °F
Supply Voltage 9.5-28VDC
Signal Output 4-20 mA two-wire, loop-powered
Maximum Output
Impedance mA 725Ω @ 24 VDC (Supply voltage -
9.5 VDC) / 0.02
Sensing Technology Precon HS-2000 capacitive
Operating Humidity 0-100% non-condensing
Operating Temperature -20° to 158°F (-29° to 70°C)
Enclosure
KHR White plastic, UL94HB
KHD Metal handy box
KHO NEMA 3R plastic box
Probe
KHR 1/2" aluminum tube with expanded
Teflon
®
filter
KHD 1/2" aluminum tube with 40 micron
stainless steel sintered filter
Wiring Terminations Screw terminals
Weight
KHR 0.2 lb (0.09 kg)
KHD 1.2 lb (0.54 kg)
KHO 0.52 lb (0.24 kg)
Approvals RoHS
Warranty 18 months
DESCRIPTION
The Kele Model KHR, KHD, and KHO Humidity
Transmitters are specifically designed for use in HVAC/BAS
applications. These instruments measure relative humidity
from 0% to 100%. The standard two-wire, 4-20 mA output
provides low cost humidity monitoring for building control.
The RH transmitter is available with thermistor or RTD
temperature sensors or a 4-20 mA rangeable temperature
transmitter. They are available in room, duct, and OSA
mounting styles.
FEATURES
Packaged for Price and Performance
Calibration free Interchangeable sensors
Twelve point computerized calibration
0% to 100% RH measurement
±3% accuracy (5% to 95% RH)
Temperature compensated
No need to remove mounting box to replace sensor
Attractive new room enclosure design
Two-wire, 4-20 mA output
Custom Logo's
Optional push button, LED and comm. jack
Optional temperature sensor (Thermistor or RTD)
RH
LOOP
+V
J5
J4
SENSOR
Temperature
sensor output to
BAS Controller
12-28
VDC
4-20mA
RH
Signal
24 VDC
Power
Supply
WIRING - KHR
SPECIFICATIONS
KHR
KHO
KHD
WIRING - KHD AND KHR