497
HUMIDITY
HUMIDITY
9
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
AUTOMATION COMPONENTS BAS/HVAC RH TRANSMITTERS
A/RH1 SERIES
Supply Voltage 12-40 VDC or 24 VAC, selectable
Accuracy ±1% @ 77°F (25°C) over a
selectable 20% span from 50 to 70%,
60 to 80%, or 70 to 90% RH
Thermal Effect <0.005% per °F (<0.01 per °C)
Signal Output 4-20 mA, 0-5 VDC, 0-10 VDC
(field selectable)
Measurement Range 0% to 100%
Sensing Technology Capacitive
Operating Temperature
Room 32° to 122°F (0° to 50°C)
Duct/OSA -40° to 140°F (-40° to 60°C)
Enclosure
Room Plastic Delta-style
Duct/OSA Plastic weatherproof
Dimensions
Room 3.8"H x 2.8"W x 0.9"D
(9.8 x 7 x 2.3 cm)
Duct 3.6" (9 cm) Ø head with 8.15"L
(20 cm) probe 0.75” (1.9 cm) Ø
OSA 3.6" (9 cm) Ø head with 3.0"L
(7.6 cm) probe 1.4" (3.6 cm) Ø
Weight
Room 0.22 lb (0.1 kg)
Duct 1.2 lb (0.54 kg)
OSA 0.6 lb (0.27 kg)
Wall Pack 0.22 lb (0.1 kg)
Approvals CE, RoHS
Warranty 5 years
DESCRIPTION
Model A/RH1 Relative Humidity Transmitters provide RH
readings at ±1% accuracy using a ceramic resistive sensor
offering a 20% to 90% operating range. The transmitters
come in wall, duct, and OSA mounting styles. They have
multiple field-selectable outputs, including 4-20 mA, 0-10V,
and 0-5V signals. The supply power is also selectable as 24
VDC or 24 VAC.
FEATURES
• Accuracy of ±1%
• Duct and OSA twist-off weatherproof housing
• 24 VDC or 24 VAC power (field-selectable)
• 4-20 mA, 0-10V, or 0-5V signal (field-selectable)
• Field-calibratable
• Optional temperature sensor
SPECIFICATIONS
A/RH1-R
A/RH1-SP
A/RH1-O
A/RH1-D
WIRING
Output Selection Switches (SW 1)
4-20 mA Output
0-10 VDC Output
0-5 VDC Output
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
2 Wire Current Output Signal
3 Wire Current Output Signal
Voltage Output Signal
DC Supply Voltage
4-20 mA Output
Supply Ground / Signal Common
AC or DC Supply Voltage
0-10 or 0-5 VDC Output Signal
4-20 mA Output
4-20mA VIN COM VOUT
AC or DC Supply Voltage
Supply Ground / Signal Common
4-20mA VIN COM VOUT
4-20mA VIN COM VOUT
Output Selection Switches (SW 1)
4-20 mA Output
0-10 VDC Output
0-5 VDC Output
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
2 Wire Current Output Signal
3 Wire Current Output Signal
Voltage Output Signal
DC Supply Voltage
4-20 mA Output
Supply Ground / Signal Common
AC or DC Supply Voltage
0-10 or 0-5 VDC Output Signal
4-20 mA Output
4-20mA VIN COM VOUT
AC or DC Supply Voltage
Supply Ground / Signal Common
4-20mA VIN COM VOUT
4-20mA VIN COM VOUT
Kommentare zu diesen Handbüchern